Floor Box Build Your Own

Step 1:

Need Help?

STANDARD DEPTH 75mm: Please note that the depth of the Floor Box selected is not the standard depth. This may result in a longer lead time.

3M RULE: As the tap off is; a) more than 3m long b) unfused the circuit protective device at the distribution board should be selected to provide fault currect protection for the unfused tap off.

This is the space you require above the plate

2 OR MORE POWER PLATES: Populating the box with 2 or more power plates may lead to issues with plug tops clashing with each other depending on type of plugs to be used.

ADVISORY NOTE: Number of Sockets: As the number of sockets could allow a loading in excess of 32A the circuit protective device at the distribution board should be no greater than 32A to provide overload protection for the 32A unfused tap off.